Fluke 355 Clamp Meter, 2 kA 2 kA 1000 V dc 600 V ac CAT IV, CAT III Non-Contact Voltage Detector

ไม่พร้อมจำหน่ายในตอนนี้
ขออภัย เราไม่ทราบว่าสินค้านี้จะกลับมาในสต็อกเมื่อใด
RS Stock No.:
411-970
Distrelec หมายเลขบทความ:
176-43-463
หมายเลขชิ้นส่วนของผู้ผลิต / Mfr. Part No.:
FLUKE 355
ผู้ผลิต:
Fluke
ค้นหาผลิตภัณฑ์ที่คล้ายกันโดยเลือกคุณลักษณะอย่างน้อยหนึ่งรายการ
เลือกทั้งหมด

Brand

Fluke

Product Type

Clamp Meter

Resistance Resolution

100mΩ

Maximum DC Current Measurement

2kA

Maximum AC Voltage Measurement

600V ac

Maximum DC Voltage Measurement

1000V dc

Maximum Resistance Measurement

400kΩ

Model Number

355

DC Voltage Resolution

1 mV dc

DC Current Accuracy

±1.5 % rdg + 5 Digits

DC Current Resolution

10mA

DC Voltage Accuracy

±1 % rdg + 5 Digits

Clamp Meter Type

AC/DC Clamp Meter

AC Current Accuracy

±3.5% +5 digits

AC Voltage Accuracy

±1 % rdg + 5 Digits

AC Voltage Resolution

1mV ac

Resistance Measurement Accuracy

1.5 % rdg + 5 Digits Ω (all ranges)

Minimum Operating Temperature

0°C

AC Current Resolution

10mA

Maximum Jaw Opening

58mm

Maximum Operating Temperature

50°C

Width

98mm

Standards/Approvals

RoHS

Weight

814g

Height

52mm

Length

300mm

True RMS

Yes

Functions Measured

AC Voltage, DC Current, DC Voltage, Frequency, Continuity, AC Current, Resistance

Safety Category Voltage

600V, 1V

Display Type

LCD

Battery Type

AA

Safety Category Level

CAT IV, CAT III

Battery Life

100h

Non-Contact Voltage Detector

Yes

Power Source

Battery

Maximum AC Current Measurement

2kA

Maximum Conductor Size

58mm

สถานะRoHS: ได้รับการยกเว้น

COO (Country of Origin):
CN

Fluke Clamp Meter, 2000A Maximum AC Current, 1000V Maximum DC Voltage - FLUKE 355


This clamp meter is a battery-powered test instrument designed for high-current AC and DC measurements in industrial and utility environments. It provides true‑RMS measurement capability, a non-contact voltage detector, frequency and continuity functions, and safety ratings suitable for high-energy systems.

Features and Benefits:


• 2000A AC+DC measurement supports heavy-current circuits
• 58mm jaw enables clamping around large conductors
• True‑RMS acquisition delivers accurate readings under distortion
• Inrush mode captures motor and inductive surge currents
• 1000 V DC and 600 V AC ranges permit multi-voltage testing
• 100 h battery life from AA cells for prolonged field use

Applications


• Suitable for utility high-current fault diagnosis
• Ideal for commissioning large motors and starters
• Used with distribution panels requiring safety category IV testing
• Can be used for frequency checks up to 1 kHz
• Useful for continuity and resistance checks on plant cabling

What accuracy can I expect for voltage and resistance measurements?


Voltage accuracy is 1% of reading Plus digits for DC and AC within 10 Hz-100 Hz and resistance accuracy is 1.5% of reading Plus digits across ranges to 400 kΩ.

How does the tool handle noisy or distorted waveforms?


The instrument uses true‑RMS measurement and offers a low‑pass filter to stabilise readings on noisy loads.

What are the environmental operating limits for on-site use?


It operates between 0 °C and 50 °C with humidity up to 95% non‑condensing and an operating altitude limit of 2000 m.

What safety categories and input protections are provided?


The device is rated to CAT IV 600 V and CAT III 1000 V with test leads rated to 1000 V and drop‑tested to 1 m.

What frequency measurement capability is available for troubleshooting?


Frequency measurement spans 5.0 Hz to 1 kHz with resolution down to 0.1 Hz and accuracy specified across the two frequency bands.

ลิงก์ที่เกี่ยวข้อง